First of all, the solenoid valve to the controlled medium (pressure for the solenoid valve to use the middle value of the pressure range of liquid, gas and air) to add up the solenoid valve coil current. If the general type solenoid valve controlled medium has on-off state or on-off state change, the solenoid valve is good, otherwise it is bad.
But sometimes baccara solenoid valve is not because the solenoid valve is broken, but because of other factors caused by the solenoid valve failure, then how to deal with?
The solenoid valve cannot work after it is energized:
Confirm the car PC solenoid valve power connection is not correct → reconnect the power and socket.
Confirm the power supply voltage within the ± working range → adjust to the normal working range.
Should the steel coil be welded again?
Coil short circuit → replace the coil.
Whether the operating pressure difference is inappropriate → adjust the pressure difference → replace the corresponding solenoid valve.
Liquid temperature is too high → replace the proportional solenoid valve.
The main valve core and moving core of the solenoid valve with impurities stuck → cleaning, if the seal is damaged, the seal should be replaced and the filter installed.
The liquid viscosity is too high, the frequency is too high, and the life has reached → the liquid oil of the product is replaced.
Solenoid valve can not automatically close:
Main spool or iron moving core seal damage → replace the seal.
Whether the liquid temperature and viscosity are too high → replace the corresponding solenoid valve.
Containing impurities solenoid valve production spool or moving iron core - cleaning.
Marbles have reached the end of their useful life or have been deformed.
Flow regulating hole blockage → timely cleaning.
Too many operations or the service life has reached → Change the product or upgrade the product.
Leakage of solenoid valve:
Internal leakage → check whether the seal is damaged, whether the spring is not installed well.
Leakage → loose joint or seal failure → tighten screw or replace seal.
Electric noise → loose wire head, tighten. Voltage fluctuation after voltage regulation is not allowed. If there are impurities or irregularities on the absorption surface of the core, it should be cleaned or replaced in time.